TYPE KX - PFA INSULATED CABLE

Siccet Siccet
TYPE KX - PFA INSULATED CABLE


DESCRIPTION
PFA insulation - overall screen - PFA jacket (IEC colour code)

APPLICATION
Temperature up to 260 °C and/or in aggressive chemical environment

CONSTRUCTION
- Reference standard: IEC 60584
- Conductor: solid or stranded
- Insulation: PFA
- Core laying-up: twisted conductors
- Extra layer: polyester tape
- Screen: aluminium/polyester bonded tape with tinplated copper drain wire
- Outer jacket: PFA
- Armour: stainless steel 304 braid
- Working temperature: -200/+260 °C
- Insulation resistance: > 20 Mohm x km (measured at 1000 Volt dc @ 20 °C)

ALTERNATIVE VERSION
- ASTM E230 (ANSI MC96.1-1982)
- DIN 43714
- BS 1843
- NFC 42324
- JIS C 1610-1981